Ralph/Peter: Many thanks for your comments. From your discussion points and what I’ve read thus far, it seems that 6/8 ACH occupied, 4 ACH unoccupied (with area sensors) is a good approach. Thank you, again.

 

ALFRED M. BOUZIANE | Project Manager

Environmental Health and Safety

A Department of Career and Protective Services

University of Southern California

 

From: DCHAS-L Discussion List [mailto:dchas-l**At_Symbol_Here**MED.CORNELL.EDU] On Behalf Of Ralph B. Stuart
Sent: Wednesday, July 31, 2013 5:51 AM
To: DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU
Subject: Re: [DCHAS-L] Lab Ventilation (ACH)

 

> I try to avoid use of ACH as a ventilation performance criterion because the same ACH involves different volumes of air for differing floor areas and  ceiling heights.  Since these must play into the engineering design and cost, I think it best to start from the actual room size and intended use, look at supplemental exhaust that may be present (fume hoods, etc.) and use a total cfm performance requirement, especially when dealing with design considerations and engineers.

 

This is an interesting point that we run into on a regular basis here at Cornell Ithaca. The ACH rates I mentioned earlier are those that we use to operate existing laboratories. This does create confusion when discussing ventilation with engineers who are designing new laboratories and laboratory renovations, who prefer Peter's approach.

 

The reason we in EHS prefer to think in terms of ACH is that this gives us a clue as to how quickly we can expect a specific chemical release to be cleared from the laboratory air, whereas design parameters for total CFM require the other information Peter mentions to give us that information. But it is an ongoing source of confusion in lab ventilation discussions with different stakeholders…

 

- Ralph

 

Ralph Stuart CIH

Chemical Hygiene Officer

Department of Environmental Health and Safety

Cornell University

 

rstuart**At_Symbol_Here**cornell.edu

 

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.