From: "Ralph B. Stuart" <rstuart**At_Symbol_Here**CORNELL.EDU>
Subject: Re: [DCHAS-L] Fume hoods
Date: May 16, 2013 12:50:32 PM EDT
Reply-To: DCHAS-L <DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU>
Message-ID: <864BD2AA7ACA3B4185B8CF3C5DD3EC2C2E60ED29**At_Symbol_Here**bscexchange1.bsc.bluefieldstate.edu>


> Do the combination sash with lockable panels help with the misuse by student ? 

 

I have observed combination sashes in use in a variety of labs on a variety of campuses and would say no. They are almost always operated with the process occurring behind the open part of the horizontal sash, so that there is no sash between the process and operator. The additional complicating factor is that many alarm systems track the open face area, resulting in alarms that seem to occur randomly as the sashes are adjusted, resulting in people being reluctant to move the sashes horizontally.

 

- Ralph

 

 

Ralph Stuart CIH

Chemical Hygiene Officer

Department of Environmental Health and Safety

Cornell University

 

rstuart**At_Symbol_Here**cornell.edu

 

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.