From: "Tsiakals, Nicholas John" <tsiakals**At_Symbol_Here**ILLINOIS.EDU>
Subject: Re: DCHAS-L**At_Symbol_Here**LIST.UVM.EDU: CODE REQUIREMENTS FOR NITROGEN UTILITY
STATIONS IN A BUILDING
In-Reply-To: <4C358643.8648.0091.0**At_Symbol_Here**ph.lacounty.gov>

This may be more than you're looking for, but here goes:

"Just install the detection system" might sound like a good / prudent thing
 to do, but there are some drawbacks.  With the information on the table, I
 would put "Just install it" under the "blindly over-controlled" column.  (
By "blind" I mean "blind with respect to what is strictly necessary" or "bl
ind w.r.t. how much control is enough control".)  Be aware that when bills 
come due and money gets tight, decision-makers can very easily cut the inst
allation or maintenance costs on such systems - where's the justification? 
 

So the challenge is to develop a good understanding of what is an acceptabl
e risk:  What control measures are necessary to sufficiently control the ha
zard?  Where is "the line", and how far beyond the line should we be?  A mo
re robust rationale than "it's easy enough to do" is to run reasonable scen
arios to describe the risk in the current scheme.  What would it take to de
velop an Oxygen Deficient Condition at any one of these utility stations?  
At any neighboring offices?  How likely is such a scenario?  For instance, 
if you know it would require a very noticeable (think: loud) leak for 20 mi
n in a busy hallway, then you may reasonably conclude a detection/alarm sys
tem would be overly redundant.  On the other hand, if a small bleed could r
esult in an ODH at a desk, then the detection/alarm system would seem very 
justifiable.

Recognize that an alarm system is an administrative control.  What action d
oes it call for someone to perform?  If the detection system is connected t
o emergency ventilation or shut-offs, now we are talking engineering contro
ls.  So I would urge you to work forward through the hierarchy of controls:
  elimination - substitution - engineering controls - administrative contro
ls - personal protective equipment.  Are there design phase (engineering co
ntrol) solutions which make the administrative control unnecessary? 

A principal question here is, "If there were a problem, how would you know?
" followed by, "How likely is it that a problem occurs?"

Hope this helps,
-Nick

-----Original Message-----
From: DCHAS-L Discussion List [mailto:DCHAS-L**At_Symbol_Here**LIST.UVM.EDU] On Behalf Of Er
ic Clark
Sent: Thursday, July 08, 2010 10:02 AM
To: DCHAS-L**At_Symbol_Here**LIST.UVM.EDU
Subject: Re: [DCHAS-L] DCHAS-L**At_Symbol_Here**LIST.UVM.EDU: CODE REQUIREMENTS FOR NITROGEN
 UTILITY STATIONS IN A BUILDING

Vic, 
Consider installing a low oxygen alarm; www.enmet.com probably has what you
 need.  We have a similar situation using plumbed in CO2.  As far as regula
tory backup to justify this very minor expense, OSHA's General Duty Clause 
29 CFR 654, 5(a)1 likely covers that - especially since you've already iden
tified the specific hazard.    
Eric 

Eric Clark, MS, CCHO, CHMM 
Safety & Compliance Officer 
Los Angeles County Public Health Lab 

>>>  7/7/2010 8:44 AM >>>
We are constructing a two-story building approximately 168 ft x 32 ft x 14 
ft high on the lower floor. The building will be multi-use, with offices in
 one portion and maintenance facilities adjoining. There will be six utilit
y stations in the building with nitrogen piped to each utility station alon
g with other utilities. The nitrogen supply line at each utility station wi
ll be a one-inch diameter line with a ball valve, a check valve, and a glob
e valve.

Could you please alert us to any applicable codes and standards specificall
y regarding any risks associated nitrogen asphyxiation.

Thanks and best regards,

Vic
 
Victor H. Edwards, Ph. D., P. E.(TX)
Director of Process Safety
Aker Solutions

Tel: +1 (713) 270-2817
Mob: +1 (713) 724-0406
Fax:    +1 (713) 270-3195
e-mail: vic.edwards**At_Symbol_Here**akersolutions.com 
  

Aker Solutions Americas Inc.
3600 Briarpark Drive, Houston, Texas 77042-5206


This e-mail and any attachment are confidential and may be privileged or ot
herwise protected from disclosure. It is solely intended for the person(s) 
named above. If you are not the intended recipient, any reading, use, discl
osure, copying or distribution of all or parts of this e-mail or associated
 attachments is strictly prohibited. If you are not an intended recipient, 
please notify the sender immediately by replying to this message or by tele
phone and delete this email and any attachments permanently from your syste
m.

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.